Does not recognize all meters.
Ensure that the unrecognized devices are not located too far from the RF
converter and that the radio signal is not too weakened by cement or metal
walls.
Ensure that the unrecognized devices are loaded to the web server list and
that contact to the wireless M-bus devices, recognized by the web server,
is not interrupted.
Please note that some wireless M-bus devices only transmit their data at
intervals of multiple hours.
Use the web interface or the ACT531 software to ensure that the mesh network
is operational.
The blue LED doesn’t stop flashing (flashing frequency > 1x per second).
If the LED flashes 1x, this indicates a RAM error.
If the LED flashes 2x, this indicates an M-bus RF module error.
If the LED flashes 3x, this indicates an error in the RF module of the mesh
network.
If the LED flashes 4x, this indicates a flash memory error.
If the LED flashes 5x, this indicates a realtime clock error.