Basic Documentation
35 / 130
Siemens M-bus level converter and M-bus web server A6V11157985_en--_f
Smart Infrastructure 2021-06-21
6.1.2 Level converter WTX631..
The level converter has six LEDs on the front side for indicating
the operating state.
The (green) LED indicates the operational state of the device.
Flashes at 1 Hz (slowly) The device functions are set up. No
communication.
Flashes at 10 Hz (fast) Device update pending.
On The device is operational.
The (green) LED indicates the state of data transmission on the M-bus network
(terminals 9 and 10).
On Data is transmitting.
Off No data is transmitting.
The (orange) LED indicates the state of the data reception on the M-bus network
(terminals 6 and 7).
On Data is being received.
Off No data is being received.
The (red) LED indicates a short circuit on the bus, very high traffic or collision rate
The (orange) LED indicates bus load that may prevent correct operation.
On Bus overload that may prevent correct operation.
Off No bus overload recognized.
The (green) LED indicates the state of power supply on the level converter.
On The device power supply is available.
Off The device power supply is not correct or unavailable.
Run
TX M-bus
RX M-bus
Short circuit
Overload
Power