Settings Files/Services
Select the check box or boxes alongside the files and services to be sent to
Synco IC. You can make multiple selections.
The following files and services are available.
Billing file: This file includes the consumption data and device
information from devices such as
wireless and wired meters and sensors.
Alarms: Web server alarms transmitted to Synco IC. In addition, the
last corresponding alarm file is saved in Synco IC. An email
notification is sent per Synco IC user settings
as soon as the web server detects an alarm.
The billing files and alarms are enabled by default.
Click Save to save your entries.
Set report interval
Select the interval for generating a report.
The following options are available:
Daily: The report is generated daily at the present post time for the
previous 24 hours.
Weekly: The report is sent each Monday at the present post time for
the last week.
Monthly: The report is generated on the first day of the month at the
present post time for the last month.
Default settings:
Billing file: Monthly
Alarms: Daily
Click Save to save your entries.
Report type
You must select the report type to generate automatic reports:
Custom report
Standard report
Report "All data"
A custom report is generated by default.
Details on report types is available in Section "Creating reports", pg. 116.
Click Save to save your entries.