Basic Documentation
106 / 130
Siemens M-bus level converter and M-bus web server A6V11157985_en--_f
Smart Infrastructure Web server browser operation 2021-06-21
Devices that are not saved are rejected.
The following must be listed at a minimum for any found device:
Serial number
Medium
Manufacturer code with optional device image
Automatically generated device name
12.4.5 Inputs/outputs
The web server has three digital inputs (I1, I2, I3) and 2 digital outputs (O1, O2).
The following settings are possible on each digital input and output:
Description: Each input/output can be labeled with an individual name.
Add to log: Select whether to log a change of state to an input/output in the
event log:
– Never
– Open: Only if the state is open or changes to open.
– Closed: Only if the state is closed or changes to closed.
– Open/close: For any change of state.
Email: Select whether to send an email (see Settings / System / Alarms), if the
input/output registers a change of state:
– Never
– Open: Only if the state is open or changes to open.
– Closed: Only if the state is closed or changes to closed.
– Open/close: For any change of state.
You can also select the output state for an output after a loss of power:
Hold the last output state.
Set to default state "open".
Click Save to save the edited settings.
Important
Digital inputs/outputs