Data Sheet for Product
32
Siemens
023_A6V11905989_en
2022-01-
07
Ball valve
Fig. 2: Fig. 6: Integrating with ball valves (recommended up to and including DN25)
Fig. 3: Fig. 7: Integration for circuits with mixing; placement of the temperature sensor
Fig. 4: Fig. 8: Integration for circuit with e.g. throttling circuit (flow sensor in the direction of flow prior to
control valve / differential pressure controller)
Please note the following torques for tightening screws and bolts on the meter:
● Screws on lock to the device cover (Fig. 1, No. 4): At least 1 Nm
● All other screws: Hand tighten, ca. 0.5 Nm
Required position for the cooling energy meter
To avoid the formation of condensation on cooling energy or combined heat/cooling energy
meters, make sure the cover on the measuring tube points to the side or downward. Install
the protection pockets so that the temperature sensor is horizontal or vertical, pointing down.
Forms a loop down using the connected wires. Mount the processor unit away from the flow
measuring section (e.g. on the wall). Make sure that condensation cannot run along the
connected lines, entering the processor unit (forming a loop downward).
Permissible mounting position when metering cooling energy:
Fig. 5: Transducer cover
Fig. 10: Recommended mounting position for cooling energy meters and combined heat/cooling energy
meters