Data Sheet for Product
16
Siemens
023_A6V11905989_en
2022-01-
07
Connection terminals
2-pin or 4-pin terminals are used to connect external cables to the modules.
● Stripping length: 6 mm
● Choice of connections:
– Fixed or flexible, 0.14…1.5 mm²
– Flexible with ferrules with plastic sleeve, 0.25…1.5 mm²
– Flexible with ferrules without plastic sleeve, 0.25…1.0 mm²
– Wire sizes 26…14 AWG
● Recommended screwdriver: 0.6 × 3.5 mm
● Torque: 0.35…0.4 Nm
The exterior diameter must be between 4 and 6 mm. All wiring must be able to be guided to
the meter through the existing bushings.
Do not connect shielded cables on the meter side (connect to one end only).
Pulse output module T45-PULSE
Function description
The pulse output module T45-PULSE enables the meter to communicate with a pulse
collector to transmit measured values. It supplies pulses that can be derived from the
energy, volume, tariff register 1 or tariff register 2. Two channels are available; their function
can be adapted using the service software 'UltraAssist'.
The outputs are in the form of standard pulses or "high-resolution pulses".
The pulse output module T45-PULSE enables the output of pulses to 2 configurable
channels.
On channel 1 (terminal 16, 17), proportional pulses can be provided:
● Energy (CE)
● Volume (CV) or
● Tariff register 1 (C1)
On channel 2 (terminal 18, 19), proportional pulses can be provided:
● Volume (CV)
● Tariff register 1 (C1) or
● Tariff register 2 (C2)
NOTICE
The output mode as well as standard/high-resolution pulses can be configured with the
service software.