Data Sheet for Product

18
Siemens
023_A6V11905989_en
2022-01-
07
NOTICE
An external antenna is required for RF module T45-RADIO-EXT with an SMA connection,
e.g. WZU-ANT-MAG or WZU-ANT-WALL.
The RF intelligence resides in the meter, the module is only responsible for communications.
The RF meters are set by default to 'stationary'.
Data output conforming to OMS
The following data is available:
Stationary read out (F000)
Transmission interval 15 min
Current energy
Current volume
Current power
Current flow rate
Current temperatures heat and cold side
Error (manufacturer-specific)
Current time stamp (type I)
Mobile read out (F001)
Transmission interval 30 s
Current energy amount
Current volume
Prev. month value energy
Prev. month value volume
Save time last previous month
Prev. year value energy
Save day last previous year
Error flags
Meter time
Other data telegrams on request.
The applicable read out type must be indicated when ordering the RF module (stationary,
mobile).
Pulse inputs
Pulse input set T45-PULSE
Function description
The meter has two pulse inputs to count external volume pulses, e.g. as generated from a
chilled water meter and/or hot water meter.
Pulse inputs can be supplied via various communication modules and optical interfaces.
Meter readings of the pulse inputs can also be displayed on the LCD.
The pulse inputs must be activated by the service software.