User's Manual
IEC 870-5-101/IEC 870-5-104 telecontrol protocol24
The SIPLUS RIC bundles usually comprise:
•CPU
• Interface/communication module (if necessary)
•Memory card
• CD with library and registration code.
SIPLUS RIC products require additional material to establish
telecommunication links, e.g. TCP/IP converters – serial,
dedicated line modems, media converters, TCP/IP routers,
SCALANCE S612 and S613 security modules, switches, cables
etc.
In order to implement telecontrol networks, basic topologies
including point-to-point, multi-point, star and ring can be con-
figured using classic or TCP/IP-based media. These can be
combined flexibly independent from existing infrastructure.
Classic WAN media
(IEC 870-5-101 telecontrol protocol)
• Dedicated line via modem, e.g. SINAUT MD2
• Dedicated line over fiber-optic cables
• Private wireless networks
TCP/IP-based WAN media
(IEC 870-5-104 telecontrol protocol)
• Ethernet networks, e.g. SCALANCE X with fiber-optic
cables
• Industrial Wireless LAN with SCALANCE W
• Public networks and the Internet using DSL and/or GPRS
• Satellite communication, e.g. with Inmarsat
IEC 870-5-104 - example of TCP/IP-based WAN with GPRS radio network (star topology)
SCALANCE
S613
IEC 870-5-104
Ethernet
IEC 870-5-104
IEC 870-5-104
IEC 870-5-104
IEC 870-5-104
RTU S7-400
CP 443
MD741
MD741 MD741
G_PCS7_XX_00270
Third-Party RTU
Control center
SIMATIC PCS 7 TeleControl
Internet
Star via
wireless
DSL router
RTU S7-300
with CP 343
RTU ET 200S
with IM 151-8
PN/DP CPU
GPRS
radio network
© Siemens AG 2011