DNP3 telecontrol protocol20
DNP3 telecontrol protocol
Widely distributed outstations (RTUs) can be controlled and
monitored with the DNP3 telecontrol protocol via serial or
Ethernet TCP/IP communication links by means of the tele-
control center in SIMATIC PCS 7. The control center integrated
with SIMATIC PCS 7 TeleControl into the operator system of
the process control system is the master during telecontrol
communication.
The slaves are represented by the outstations. SIMATIC
S7-300/S7-300F and S7-400/S7-400F/S7-400H/S7-400FH
controllers as well as third-party RTUs can be used as out-
stations.
Further hardware and software components round off the
range of products:
TIM communication modules
•TCP/IP converters serial and MD modem modules
•GSM/GPRS components
TCP/IP routers and switches
SCALANCE S612 and S613 security modules
Dedicated-line accessories
•Cables
Engineering package for configuration of DNP3 data
objects, stations, networks and connections as well as
for diagnostics
In order to implement the telecontrol networks, the basic
topologies of point-to-point, multi-point, star and ring can be
configured using classic or also TCP/IP-based media, and com-
bined flexibly independent of the infrastructural conditions.
DNP3 - example of classic dedicated network (star + multi-point topologies)
Classic WAN media
Dedicated line via modem, e.g. SINAUT MD2
Private wireless networks
Analog telephone network
Digital ISDN network
Mobile radio network GSM
RS 485
MD2 MD2
· · ·
· · ·
MD2
G_PCS7_XX_00267
MD2
MD2
MD2
Ethernet
MD2
Control center
SIMATIC PCS 7 TeleControl
DNP3 master
Dedicated network
with star topology
Range without repeaters (example)
with conductor cross-section 0.8 mm
- 1 200 bit/s max. 33 km
- 2 400 bit/s max. 27 km
- 19 200 bit/s max. 11 km
Star +
multi-point
TIM 3V-IE
DNP3 (slave)
TIM 3V-IE
DNP3 (slave)
TCP/IP to serial
converter
TIM 4R-IE
DNP3 (slave)
TIM 4R-IE
DNP3 (slave)
RTU S7-300
RTU S7-300
RTU S7-400H RTU S7-400
© Siemens AG 2011