Data Sheet for Product

17
Building Technologies
CE2N5323_en--_b
2018-01-23
Wireless meters
ACT50 is used to configure the wireless modules.
Wireless operation is activated via the WFZ-PS radio telegram tool or the ACT50 software.
Wired meters
Since the M-bus module adopts all parameters from the meter, only the primary address can
be configured via the M-bus system.
The power required for operation is supplied by the M-bus system, but the module is
equipped with a battery. It powers the module when there is no power available from the M-
bus.
The modules do not affect the acquisition of consumption data and, for this reason, can be
retrofitted at any time without damaging the seal.
Sealing
After mounting the meter, all components must be sealed to prevent tampering (observe
national regulations):
The flow measuring section with its fitting (inlet)
The flow temperature sensor with the ball valve or the immersion pocket, the immersion
pocket with the pipe and, if required,
The module with the processor
Type summary
Features of the impeller type meters listed below:
Mounting location Return
Design Processor combined with flow measuring section
Rated pressure PN 16
Sensor mounting Return sensor, integrated in the flow measuring section
Temperature sensor type Pt1000, Ø 5.0 mm, length 45 mm
Temperature sensor cable
length
1.5 m
Communication IrDA interface
Threshold value for:
Acquisition of heating 1.0 K
Acquisition of cooling
energy
0.2 K
Due date 31.12
Display kWh
Heat meter
Options
Order number
Type
0.6 m
3
/h, mounting length
110 mm,
connecting thread G ¾"
S55561-F177 WFM501-E000H0
1.5 m
3
/h, mounting length
110 mm,
connecting thread G ¾"
S55561-F178 WFM502-E000H0
2.5 m
3
/h, mounting length
130 mm,
connecting thread G 1"
S55561-F179 WFM503-J000H0