Data Sheet for Product

10
Siemens A6V10564480_en--_h
Smart Infrastructure 2021-06-17
Notes
NOTICE
Note the following when servicing a ball valve/rotary actuator:
Switch off both pump and operating voltage.
Close shutoff valves.
Release pressure in the pipes and allow them to cool down completely.
Disconnect electrical connections from the terminals as needed.
The rotary actuator must be properly installed prior to recommissioning the ball valve.
Ensure that there is no cavitation
Install filter to increase functional security
Technical design/mechanical design
The Siemens 6-port control ball valve has an internal pressure equalization function that
ensures the safe operation of heated and chilled ceilings in a closed valve state (45°
position) Changes to media temperature in the heated and chilled ceiling can result in over
or under pressure in a closed state and may, under certain circumstances even damage part
of the heated and chilled ceiling.
The safety function only acts in the closed valve position (45°). The heating and cooling
circuits are safely separated while operating.
Safety
CAUTION
National safety regulations
Failure to comply with national safety regulations may result in personal injury and property
damage.
Observe national provisions and comply with the appropriate safety regulations.
NOTICE
Use of rotary actuator
Commission the 6-port control ball valve only after it is correctly coupled with the rotary
actuator.