Data Sheet for Product
15
Siemens A6V10564480_en--_h
Smart Infrastructure 2021-06-17
Examples of device combinations
Hydraulically balanced solution with 6-port ball valve as changeover and PICV as the
control element
In this application, the 6-port ball valve changes over between 100% cooling or 100%
heating. The PICV valve controls the primary flow for the application.
The following combinations are possible:
A
6
V
1
0
5
6
4
4
8
0
_
Z
1
2
A
6
V
1
0
5
6
4
4
8
0
_
Z
1
1
DN20:
1. VWG41.20-4.25-4.25 (1” 6-port ball valve) and GDB341.9E (rotary actuator)
2. VPP46.20 (PICV) and SSA61 (0...10 V actuator)
DN10:
1. VWG41.10-1.9-1.9 (1/2” 6-port valve) and
GDB341.9E (5Nm) / GSD341.9A (2Nm) (rotary actuator)
2. VPP46.15 (PICV) and STA63 (0...10 V actuator)
Dimensions
D = Nominal size
H = Total height of actuator to
wall or ceiling, for mounting,
connection, operation,
maintenance, etc.
H1 = Dimension from the pipe to
the center to install actuator
(upper edge)
Type DN B C D G L1 L2 H H1 H2 H3 H4 H5 Weight
[mm] [mm] [mm] [inch] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [kg]
VWG41.10.. 10 25 50.2 42 G1/2" 32.5 67.5 >305 45.4 36.4 45 27.5 104.1 0.78
VWG41.20.. 20 38 67.2 42 G1“ 40.5 86.5 >310 51.9 43 60 36.4 134.5 1,796