Product Overview
5/8
Siemens 2-port and 3-port valves with T-bypass PN 16 CE1N4854en
Building Technologies 17.12.2010
90°
4362Z01
90°
Commissioning notes
Commission the valve only if the manual knob or actuator has been mounted
correctly.
The straight-through path A AB can be opened electrically via the actuator, or
manually. With 3-port valves, this throttles or closes T-bypass B.
Manually, path A
AB can only be opened to 70 % (T-bypass closes to 30 %).
The valves are closed by a return spring.
Maintenance
V..P45..S valves require no maintenance.
When doing service work on the valve / actuator:
Deactivate the pump and turn off the power supply
Close the shuttoff valves
Fully reduce the pressure in the piping system and allow pipes to completely cool
down
If necessary, disconnect the electrical wires.
Before putting the valve into operation again, make certain the manual knob or the
actuator is correctly fitted.
The stem sealing gland cannot be exchanged. In the case of leakage, the entire valve
must be replaced. Contact your local office or branch.
Disposal
Before disposal the valve must be dismantled and separated into its various constituent
materials.
Legislation may demand special handling of certain components, or it may be sensible
from an ecological point of view.
Current local legislation must be observed.
Warranty
The technical data given for these applications is valid only in conjunction with the
Siemens actuators as detailed under «Equipment combinations».
All terms of the warranty will be invalidated by the use of actuators from other
manufacturers.
Orientation
Manual adjustment
.
Warning
Stem sealing gland