Data Sheet for Product

2
Siemens
CE1N4402en
Smart Infrastructure 2022-03-
04
Use
In boiler, district heating and refrigeration plants, heating groups, ventilation and air-handling
units as control or shutoff valves.
For use in closed circuits.
Type summary
Valves Actuators SAX..
1)
SKD.. SKB.. SAV..
1)
SKC..
Stroke 20 mm 40 mm
PN 16 Positioning force 800 N 1000 N 2800 N 1600 N 2800 N
Data sheet N4501 N4561 N4564 N4503 N4566
-10...150 °C
Stock no. DN k
vs
S
v
Δp
s
Δp
max
Δp
s
Δp
max
Δp
s
Δp
max
Δp
s
Δp
max
Δp
s
Δp
max
[m
3
/h] [kPa]
VVF32.15-1.6 S55202-V100 15 1.6 > 50 1000 400 1000 400 1000 400 - - - -
VVF32.15-2.5 S55202-V101 15 2.5
VVF32.15-4 S55202-V102 15 4
VVF32.25-6.3 S55202-V103 25 6,3
VVF32.25-10 S55202-V104 25 10
VVF32.40-16 S55202-V105 40 16 > 100 550 750 1000 400
VVF32.40-25 S55202-V106 40 25
VVF32.50-40 S55202-V107 50 40 350 300 450 750
VVF32.65-63 S55202-V108 65 63 200 150 250 200 700 450
VVF32.80-100 S55202-V109 80 100 125 75 175 125 450 250 225
VVF32.100-160
2)
S55202-V110 100 160 - - - - - - 160 125 300 250
VVF32.125-250
2)
S55202-V111 125 250 125 90 190 160
VVF32.150-400
2)
S55202-V112 150 400 80 60 125 100
1)
Suitable for medium temperatures up to 130 °C.
2)
Valve characteristic for k
vs
value 100 m
3
/h from 70% stroke, k
vs
value 160 m
3
/h from 85% stroke, and k
vs
value
400 m
3
/h from 90 % stroke is optimized for maximum volumetric flow.