Data Sheet for Product
Table Of Contents
14
Siemens
CE1N4402en
Smart Infrastructure 2022-03-
04
Standards, directives and approvals
Flanges ISO 7005
Length of flanged valves DIN EN 558-1, line 1
Valve characteristic
1)
VDI 2173
Leakage rate Throughport, bypass according to EN 60534-4 / EN
1349
Water treatment VDI 2035
Environmental conditions
Storage IEC 60721-3-1
Class 1K3
Temperature -15…55 °C
Rel. humidity 5…95 % r.h.
Transport IEC 60721-3-2
Class 2K3, 2M2
Temperature -30…65 °C
Rel. humidity < 95 % r.h.
Operation IEC 60721-3-3
Class 3K5, 3Z11
Temperature -15…55 °C
Rel. humidity 5…95 % r.h.
Umweltverträglichkeit
The product environmental declaration CE1E4402en01 (VVF32..)
3)
and CE1E4402en02 (VXF32..)
3)
contains
data on environmentally compatible product design and assessments (RoHS compliance, materials composition,
packaging, environmental benefit, disposal).
Dimensions / Weight
Dimensions
See Dimensions [▶ 15]
Weight
See Dimensions [▶ 15]
1)
For certain valve lines and high k
vs
values, the valve characteristic is optimized for maximum volumetric flow
k
V100
.
2)
Valves where PS x DN < 1000, do not require special testing and cannot carry the CE label.
3)
The documents can be downloaded from http://www.siemens.com/bt/download.