Data Sheet for Product
Table Of Contents
10
Siemens
CE1N4402en
Smart Infrastructure 2022-03-
04
Medium compatibility and temperature ranges
Medium Temperature range Type Notes
T
min
T
max
V..F32..
[°C]
Cold water 1 25 x -
Low-temperature hot water 1 130 x -
High-temperature hot water
1)
130 150 x -
Water with antifreeze -5 150 x For medium temperatures below 0°C,
the stem heating ASZ6.6 has to be
installed.
-10 150 x
-20 150 -
Brines -5 150 x For medium temperatures below 0°C,
the stem heating ASZ6.6 has to be
installed.
-10 150 x
-20 150 -
Demineralized water
according to
VDI2035 / SWKI_BT102-01
1 150 x -
1)
Differentiation due to saturated steam curve
Fields of use
Fields of use Type
VVF32.. VXF32..
Generation Boiler plants x x
District heating plants x -
Refrigeration plants x x
Distribution Heating groups x x
Ventilation and air-handling
units
x x