Data Sheet for Product

5
Siemens A6V11877580_en--_c
Smart Infrastructure 2020-10-08
Valve characteristic
Since the VQP/VQI is an On/Off PICV, the valve characteristic is not based on a modulating
function. The valve characteristic is made up of two operating points:
The PICV is closed at stroke H/H
100
= 0 and volumetric flow V/V
100
= 0
The PICV is open at stroke H/H
100
= 1 and volumetric flow V/V
100
= 1
Type summary
Type Stock no. DN H
100
Connections Test points
min 100
[mm] [inch] P/T-ports [l/h] [l/h]
VQP46.10L0.5 S55264-V134
10
4
G ½
Externally
threaded
No
30 520
VQP46.10L0.5Q S55264-V133 Yes
VQP46.15L0.5 S55264-V138
15 G ¾
No
VQP46.15L0.5Q S55264-V137 Yes
VQP46.15F1.3 S55264-V142 No
300 1300
VQP46.15F1.3Q S55264-V141 Yes
VQP46.20F1.5 S55264-V146
20 G 1
No
320 1500
VQP46.20F1.5Q S55264-V145 Yes
VQP46.25F1.8 S55264-V150
25 G 1 ¼
No
620 1800
VQP46.25F1.8Q S55264-V149 Yes
Type Stock no. DN H
100
Connections Test points
min 100
[mm] [inch] P/T-ports [l/h] [l/h]
VQI46.15L0.5 S55264-V136
15
4
Rp ½
Internally
threaded
No
30 520
VQI46.15L0.5Q S55264-V135 Yes
VQI46.15F1.3 S55264-V140 No
300 1300
VQI46.15F1.3Q S55264-V139 Yes
VQI46.20F1.5 S55264-V144
20 Rp ¾
No
320 1500
VQI46.20F1.5Q S55264-V143 Yes
VQI46.25F1.8 S55264-V148
25 Rp 1
No
620 1800
VQI46.25F1.8Q S55264-V147 Yes
DN = Nominal size
H
100
= Nominal stroke
min
= Smallest pre-settable volumetric flow through fully open valve (H
100
)
100
= Volumetric flow through fully open valve (H
100
)
Delivery
PICVs, actuators and accessories are packaged and supplied separately.