Data Sheet for Product
12
Siemens A6V11877580_en--_c
Smart Infrastructure 2020-10-08
Assemble
1. Insert the differential pressure
regulator and tighten the
regulator to stop
2. Loosen the differential pressure
regulator until the marking on the
regulator is aligned against the
flow direction
3. Orient the indicator in fully open
position to presetting
Re-adjust Step 2 if necessary
4. Insert the On/Off bonnet and
tighten with 20 Nm
Sealing gland
The stem sealing gland cannot be exchanged. Should leakage occur, the whole valve must
be replaced.
Disposal
WARNING
Tensioned return spring
Opening the valve housing can release the highly tensioned return spring,
which can cause flying parts and injuries.
●
Do not open the valve housing.
The valve should not be disposed of as domestic garbage.
● Special treatment for individual components may be required by law or make ecological
sense.
● Comply with all local and currently applicable laws and regulations.
Warranty
Technical data on specific applications are valid only together with Siemens products listed
under "Equipment combinations". Siemens rejects any and all warranties in the event that
third-party products are used.