Data Sheet for Product

6 / 14
Siemens Combi valves PN 16 with flanged connections A6V11213406_a
Building Technologies 2017-11-24
Sizing
Basis of design
1. Determine heat demand Q [kW]
2. Determine temperature spread ΔT [K]
3. Calculate volumetric flow
[
]
[]
ú
û
ù
ê
ë
é
D×
×
=
h
l
KT163.1
1000kWQ
V
&
4. Select suitable Combi valve VPF43.../1
5. Determine dial setting using volumetric flow/dial presetting tables, see below.
Example
1. Heat demand Q = 150 kW
2. Temperature spread T = 6 K
3. Volumetric flow
hmhl
K
kW
/6.21/654'21
6163.1
1000150
V
3
==
×
×
=
&
Hint: You can also determine the volumetric flow using the valve slide rule.
4. Select Combi valve VPF43../1
Ideally, Combi valves should be selected such that they operate at about 80%
of their maximum flow, enabling them to deliver spare capacity, if required.
Selection: VPF43.65F24/1 p
min
= 35 kPa
VPF43.65F35/1 p
min
= 70 kPa
5. Determine dial setting using volumetric flow/dial presetting tables:
VPF43.65F24/1 Volumetric flow 21.6 m
3
/h
Dial setting 3.6
VPF43.65F35/1 Volumetric flow 21.6 m
3
/h
Dial setting 2.7
Tables to determine the dial setting for a desired volumetric flow.
Nominal flow
VPF43.50F16/1 16 m
3
/h nominal
[m
3
/h] 2.3 3 3.8 4.5 5.3 6 6.8 7.5 8.3 9 9.8 10.5 11.3 12 12.8 13.5 14.3 15
Dial Min. 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.8 3 3.2 3.4 3.6 3.8 4
kPa 6.5
6.8 7.1 7.4 7.7 8.0 8.8 9.6 10.4
11.2 12.0 13.5 15.2 16.8 18.5
20
VPF43.65F24/1 24 m
3
/h nominal
[m
3
/h]
4.4 5.6 6.6 7.7 8.6 9.6 10.5 11.5 12.5 13.5 14.7 15.8 17.1 18.5 19.9 21.5 23.2 25
Dial Min. 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.8 3 3.2 3.4 3.6 3.8 4
kPa 15 15.7 16.2 16.8 17.4 18.0 18.4 18.7 19.1 19.5 20.0 20.9 21.8 22.8 23.9 25
VPF43.80F35/1 35 m
3
/h nominal
[m
3
/h] 5.3 6.9 8.3 9.6 10.9 12.2 13.5 14.8 16.2 17.6 19.1 20.7 22.4 24.3 26.4 28.7 31.2 34
Dial Min. 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.8 3 3.2 3.4 3.6 3.8 4
kPa 16 16.4 16.8 17.2 17.6 18.0 18.4 18.7 19.1 19.6 20.0 20.8 21.7 22.7 23.8 25
VPF43.100F70/1 70 m
3
/h nominal
[m
3
/h] 12.1 15 18 21 23 25 28 30 32 35 38 40 43 47 51 56 62 68
Dial Min. 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.8 3 3.2 3.4 3.6 3.8 4
kPa 20.0 20.5 20.8 21.2 21.7 22.0 22.5 23.2 23.8 24.3 25.0 26.6 28.2 30.2 32.6 35
VPF43.125F110/1 110 m
3
/h nominal
[m
3
/h] 18.5 23 28 33 37 42 46 51 55 60 65 69 74 80 85 92 99 110
Dial Min. 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.8 3 3.2 3.4 3.6 3,8 4
kPa
16.0
16.4 16.8 17.2 17.6 18.0 18.5 19.2 19.8 20.3 21.0 23.3 25.3 28.0 30.7
35
Engineering example
Volumetric flow/dial
presetting
Standard flow rate