User Manual
2/8
Siemens Small Valves CE1N2103en
Smart Infrastructure 2020-10-06
Use
· For use in ventilation and air conditioning systems for water-side control of chilled
ceilings and terminal units in closed circuits, e.g. for induction units, fan coil units,
small re-heaters and small re-coolers.
- 2-pipe systems with 1 heat exchanger for heating and cooling
- 4-pipe systems with 2 separate heat exchangers for heating and cooling
· In closed-circuit zone heating systems, e.g. for:
- Separate floors in a building
- Apartments
- Individual rooms
Type summary
Type reference DN k
v
-value setting range [m
3
/h)
VD115CLC 15 0.25…1.9
VD120 CLC 20 0.25…2.6
VD125 CLC 25 0.25…2.6
When ordering, please give quantity, product name and type reference.
2 small valves VD120CLC
Valves, actuators and accessories are packed separately.
Equipment combinations
Product Types Data sheet
Electromotoric actuators SSA131 / SSA331 / SSA161.05
1)
A6V11858276
SSA151.05HF
1)
, SSA161.05HF
1)
A6V11858278
SSA955
2)
N2700
Thermal actuators 2-position STA23… / STA73…
N4884
Thermal actuators DC 0…10 V STA63…
1)
Preadjustment of flow rate: > 1.5 mm valve stroke.
If the valve travel is less than 1.5 mm, self-calibration is not possible and the valve with the actuator
remains blocked.
2)
Preadjustment of flow rate: > 0.5 mm valve stroke.
If the valve travel is less than 0.5 mm, self-calibration is not possible and the actuator generates an error
message.
Mechanical and technical design
The valves make possible flow rate preadjustments by limiting the stoke. A preadjusting
screw with reference numbers from 0 to 7 is located under the protective cover right by
the valve stem.
1 Gland with preadjusting ring
2 Valve insert
3 Fitting with O-ring
4 Valve plug with soft disk
5 All valves are supplied with a protective cover.
That cover facilitates shutoff when making the
plant pressure test and manual adjustments for
improvised plant
operation during the construction
phase
.
2103Z02
1
2
3
5
4
Order
Example
:
Delivery
.
.
.
.
.
.
.
.
.
.