Data Sheet for Product
Submittal Sheet BT300 VFD NEMA Type 3R Drive and Bypass
Document No. 154-131
October 16, 2018
Page 2 of 6 Siemens Industry, Inc.
Product Numbers
Your Product Number:
Example Product Number:
V B A 3 4 0 . F 3 3 0 X B T 3 0 0
Model
VB VFD
Series
A
Factory Designation
Voltage
1 208/240 V
3 380 to 480 V
HP rating
1.0, 1.5, 2.0, 3.0, 4.0, 5.0, 7.5,
10, 15, 20, 25, 30, 40, 50, 60
75, 100, 125 [See Note 1 for these selections]
Disconnect
F Fused Disconnect
NEMA rating
3 NEMA Type 3R
Contactor
0 None (Drive only)
3 Contactor Bypass (Input, Output, Bypass)
Reactor [See Note 2]
0 None
Filter
X Factory Required Designator
Options
BT300 BT300 Drive
Notes:
1. Available only with Voltage Codes 3
2. Order as a separate item for input line reactors
If a load reactor is required, a separate enclosed reactor is required.
Example Shown:
VBA340.F330XBT300 =
VBA Conventional Bypass, 480V, 40 HP, fused disconnect,
NEMA Type 3R, 3 contactors, no reactor, BT300 Drive.
Table 1. NEMA Type 3R Bypass Specifications.
NEMA Type 3R Bypass
Specification
Description
Input Voltage (3-phase)
208/240V, 3 AC ±10% 1 HP to 60 HP
480V, 3 AC ±10% 1 HP to 125 HP
Temperature
Operating: 14°F to 104°F (–10°C to 40°C), may require de-rating to 122°F (50°C)
Storage: –40°F to 158°F (–40°C to 70°C)
Humidity
0 to 95% rh, non-condensing
Table 2. NEMA Type 3R Bypass Output Current Ratings (Amps)—Per NEC Motor Tables.
HP
1
1.5
2
3
5
7.5
10
15
20
25
30
40
50
60
75
100
125
208V
3.9
5.5
7.4
10.4
16.7
22
28
42
54
68
80
104
130
154
–
–
–
240V
3.9
5.5
6.8
9.6
15.2
22
28
42
54
68
80
104
130
154
–
–
–
480V
2.1
3.0
3.4
4.8
7.6
11
14
21
27
34
40
52
65
77
96
124
156