Data Sheet for Product

Submittal Sheet BT300 VFD NEMA Type 3R Drive and Bypass
Document No. 154-131
October 16, 2018
Page 2 of 6 Siemens Industry, Inc.
Product Numbers
Table 1. NEMA Type 3R Bypass Specifications.
NEMA Type 3R Bypass
Specification
Description
Input Voltage (3-phase)
208/240V, 3 AC ±10% 1 HP to 60 HP
480V, 3 AC ±10% 1 HP to 125 HP
Temperature
Operating: 14°F to 104°F (10°C to 40°C), may require de-rating to 122°F (50°C)
Storage: 40°F to 158°F (40°C to 70°C)
Humidity
0 to 95% rh, non-condensing
Table 2. NEMA Type 3R Bypass Output Current Ratings (Amps)Per NEC Motor Tables.
HP
1
1.5
2
3
5
7.5
10
15
20
25
30
40
50
60
75
100
125
208V
3.9
5.5
7.4
10.4
16.7
22
28
42
54
68
80
104
130
154
240V
3.9
5.5
6.8
9.6
15.2
22
28
42
54
68
80
104
130
154
480V
2.1
3.0
3.4
4.8
7.6
11
14
21
27
34
40
52
65
77
96
124
156
NOTE: Drives are current rated devices. Verify that the listed ratings are the motor full load current rating.