Data Sheet for Product
8
西门子
A6V11168935_en--_d
Smart Infrastructure
2022-02-23
Product documentation
Topic
Title
Document ID
Mounting and installation
VAF41.. Mounting instructions
A5W90003152
Data sheet
VAF41.. Data sheet
A6V11168935
Environmental compatibility
Product environmental compatibility
A5W90003652
Related documents such as environmental declarations, CE declarations, etc., can also be
downloaded at the following Internet address:
www.siemens.com/bt/download
Notes
Security
CAUTION
National safety regulations
Failure to comply with national safety regulations may result in personal injury and property
damage.
● Observe national provisions and comply with the appropriate safety regulations.
Engineering
We recommend installing the ball valve in the return pipe, as the temperature is
● higher for application in cooling systems and
● lower for applications in heating systems,
which could extend the life of stem sealing gland.
Please ensure the flow is cavitation free (refer to Sizing [▶ 3]).
Please always install a strainer upstream of the valve to increase the valve's functional
safety.
Mounting
Both ball valve VAF41.. and rotary actuator GEB..1E, GIB..1E or GCA..1E can easily be
assembled on site. Normal tools and adjustment are required.
The valve is supplied with Mounting Instructions A6V11162533 (A5W90003152).
Orientation