User Manual

Control ball valve thread connection
Typical applications Actuators Data sheet
Spring return
2 Nm 5 Nm 7 Nm 10 Nm
- Air handling unit
- Domestic hot water
GQD..9A
GMA..9E
GLB..9E
GDB..9E
GSD161.9A
N4659
N4658
A6V10636203
A6V10636150
A6V10636056
GSD..9A GDB..9E GLB..9E
ü
GQD..9A GMA..9E
Control ball valve ange connection
Typical applications Actuators Data sheet
Spring return
18 Nm 25 Nm 35 Nm 70 Nm
- Air handling unit
- Domestic hot water
GCA..1E
GBB..1E
GIB..1E
N4613
N4626
N4626
GBB..1E GIB..1E 2*GIB..1E
ü
GCA..1E
PN 40 -10…120 °C
DN
∆p
s
[kPa]
∆p
max
[kPa]
∆p
s
[kPa]
∆p
max
[kPa]
∆p
s
[kPa]
∆p
max
[kPa]
∆p
s
[kPa]
∆p
max
[kPa]
N4212 N4212 N4211 N4211
VAI61.15..
VBI61.15..
15 1400 350 1400 350 1400 350 1400 350
VAI61.20..
VBI61.20.. 20 1400 350 1400 350 1400 350 1400 350
VAI61.25.. VBI61.25-10
25 1400 350 1400 350 1400 350 1400 350
VAI61.32..
VBI61.32-16 32 1000 350 1000 350
VAI61.40.. VBI61.40-25
40 800 350 800 350
VAI61.50..
VBI61.50-40 50 600 350 600 350
VAG61.15..
VBG61.15.. 15 1400 350 1400 350 1400 350 1400 350
VAG61.20.. VBG61.20..
20 1400 350 1400 350 1400 350 1400 350
VAG61.25..
VBG61.25-10 25 1400 350 1400 350 1400 350 1400 350
VAG61.32..
VBG61.32-16 32 1000 350 1000 350
VAG61.40.. VBG61.40-25
40 800 350 800 350
VAG61.50..
VBG61.50-40 50 600 350 600 350
PN 16 2…80°C
DN
∆p
s
[kPa]
∆p
max
[kPa]
∆p
s
[kPa]
∆p
max
[kPa]
∆p
s
[kPa]
∆p
max
[kPa]
∆p
s
[kPa]
∆p
max
[kPa]
Data sheet A6V11168935_a
VAF41.65-63 65 400 400 400 400
VAF41.80-100 80 400 400 400 400
VAF41.100-160 100 400 400
VAF41.125-250 125 400 400
VAF41.150-360 150 400 400
Beijing Siemens Cerberus Electronics Ltd
Building Technologies Division
No.1, Fengzhi Donglu Xibeiwang,
Haidian District, Beijing,
100094, P.R. China
Tel +86 10 6476 8806
© Siemens Ltd, 2017
Subject to changes and errors. The information
given in this document only contains general
descriptions and/or performance features which
may not always specically reect those described,
or which may undergo modication in the course
of further development of the products. The
requested performance features are binding only
when they are expressly agreed upon in the
concluded contract.