Commissioning
Programming mode
Press the programming key short (< 0,5 s) to enable pro-
gramming mode. This is indicated by the programming
LED.
Factory setting
When the programming key is pressed very long (> 20 s)
the device is reset to the default factory settings. This is
indicated by evenly flashing the programming LED. The
flashing stops after 5 seconds.
Note:
When the programming key is pressed longer (> 0,5 s to
2 s) no functions are activated.
When the programming key is pressed longer (> 2 s) the
device starts connection test. This is a special mode for
Desigo TRA. The device may be blocked for the manufac-
turer specific functions for approx. 10 seconds for the
programming mode. This is indicated by briefly flashing
the programming LED.
Installation notes
The device can be used for permanent installation in
dry interior rooms and for insertion in distribution
boards or miniature housings.
WARNING
The device must be mounted and commissioned by an
authorised electrician.
The device may be mounted in switch and socket com-
binations if VDE-certified devices are used exclusively.
The prevailing safety rules must be heeded.
For planning and construction of electric installations,
the relevant guidelines, regulations and standards of
the respective country are to be considered.
Technical data
Power supply
KNX bus voltage: via via bus coupling unit (BTM)
UP 117
KNX bus current: 8 mA
Operating elements
1, 2 or 4 pairs of horizontally arranged switch buttons
Number of switching operations: > 20000 per button
1 learning push button:
for toggling between normal mode / addressing mode
for reset the device to the default factory settings and
to activate manufacturer specific functions
Display elements
1 red LED:
for checking the bus voltage and for displaying normal
mode / addressing mode
This LED indicated also the reset to the default factory
settings and further activated manufacturer specific
functions
1 LED as orientation light in the dark
UP 28x/3 und 287/5:
1 red LED per switch button for status annunciation
(e.g. quadruple switch = 8 status LED’s