Data Sheet for Product

GAMMA instabus
Technical product information
February 2012
DELTA isystem wall switch single
wall switch double
wall switch triple
Technical manual UP 22x/2, UP 22x/3 and UP 22x/5, 8 pages Siemens AG
Infrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma Siemens AG 2012 Control Products and Systems
Subject to change without further notice P.O. Box 10 09 53, D93009 Regensburg
2.16.1.11/4
Application program
25 C0 BTM wall switch 909301
Single, double or triple wall switch for
switching on / off / toggle
bell function (press on, release off)
dimming (with one or two buttons)
solar protection control (with one or two buttons)
send value (8bit and 16bit)
send variable value (8Bit)
1bit and 8bit scene control
forced control
second transmission object
8 channel scene controller with 8 scenes per channel
1 LED as orientation light
1 LED per switch button for status annunciation
IR receiverdecoder for 16 IR channels
This application program applies to all instabus wall
switches that are mounted on a bus coupling unit (BTM)
UP 117.
When expanding the number of switch buttons or the
functionality (e.g. from UP 221/_2 to UP 223/_5) the
prior configuration remains and must only be expanded.
In the same simple fashion switching between design
lines (DELTA line / vita / miro oder DELTA style) is possi
ble.
Configuration and operation of all instabus wall switches
is identical independent of design and the number of
switch buttons
Commissioning
Programming mode
Press the programming key short (< 0,5 s) to enable pro
gramming mode. This is indicated by the programming
LED.
Factory setting
When the programming key is pressed very long (> 20 s)
the device is reset to the default factory settings. This is
indicated by evenly flashing the programming LED. The
flashing stops after 5 seconds.
Note:
When the programming key is pressed longer (> 0,5 s to
2 s) no functions are activated.
When the programming key is pressed longer (> 2 s) the
device starts connection test. This is a special mode for
Desigo TRA. The device may be blocked for the manufac
turer specific functions for approx. 10 seconds for the
programming mode. This is indicated by briefly flashing
the programming LED.