Data Sheet for Product
GAMMA instabus
Technical product information
February 2012
DELTA isystem wall switch, single
wall switch, double
wall switch, triple
Siemens AG UP 22x/2, UP 22x/3 and UP 22x/5, 8 pages Technical manual
Infrastructure & Cities Sector, Building Technologies
Control Products and Systems Siemens AG 2012 Update: http://www.siemens.com/gamma
P.O. Box 10 09 53, D93009 Regensburg Subject to change without further notice
2.16.1.11/3
[0°C....40°C], brightness value [0...2000 lux] controls
the LED for each of up to three value ranges respec
tively to either
o on
o off
o flash, slowly (0,3 Hz)
o flash, moderately (1 Hz)
o flash, fast (5 Hz)
The brightness of the orientation light is configurable
and may be controlled via object (e.g. for night opera
tion).
Additional functions of devices with status LED
Status LED
The same configuration options as for the orientation
LED are available for the status LED’s of a device.
• LED permanently off
• LED permanently on
• LED indicates IR activity (only for switch with IR re
ceiver)
• LED indicates user operation
• LED indicates long button press
• A binary status object controls the LED for each status
value on (=1) or off (=0) respectively to either
o on
o off
o flash, slowly (0,3 Hz)
o flash, moderately (1 Hz)
o flash, fast (5 Hz)
• An analog status object (8bit value [0...255], percent
value, 16bit value [0...65535], temperature value
[0°C....40°C], brightness value [0...2000 lux] controls
the LED for each of up to three value ranges respec
tively to either
o on
o off
o flash, slowly (0,3 Hz)
o flash, moderately (1 Hz)
o flash, fast (5 Hz)
The brightness of the status LED can be configured mu
tually for all status LED’s and can be influenced via object
(e.g. for night operation).
To find a switch when its associated status LED is turned
off and it is dark, this LED may be configured to cyclically
flash briefly.
Scene controller
[applies only to UP 223/5]
The scene controller enables integration of those actua
tors, which themselves do not provide 8bit scene con
trol, into 8bit scene control schemes. Up to eight scene
channels (A … H) are controlled via a single 8bit scene
object. For each channel one of these functions may be
selected:
• Switching
• Solar protection control
• Forced control
• 8bit value
• 16bit value
Each channel may be assigned to up to eight different
scene numbers (1...64).
Scenes are recalled with a short button press and saved
with a long button press.
Before saving a scene the actuators belonging to that
scene must be set to the desired light levels and switching
states.
When receiving a save telegram for an 8bit scene via the
8bit scene object the scene controller interrogates the cur
rent values and states of the actuators via the correspond
ing objects and saves these values and states as scene set
tings for the associated scene number. Saved scene values
are only deleted by a new configuration of the device if the
parameter “Delete scene memory after bus voltage recov
ery” is set to “Yes”.
IR receiver
[applies only to UP 223/5]
The device offers a 16 channel IR receiverdecoder.
As described for the single buttons / button pairs above,
each of the 16 IR channels may be either configured for
functions associated with single buttons or a button pair.
Likewise, dependent on the selected main functions ad
ditional functions may be selected. The 16 channel IR
handheld remote S425/72 allows to fully exploit these
possibilities.
The application program already has been loaded in the
factory. With the ETS (Engineering Tool Software) the
specific parameters and addresses are assigned appropri
ately, and downloaded into the device.
Function ex factory:
All switch button pairs are preconfigured for the build
ing site function for switching (left on, right off).