Data Sheet for Product
GAMMA instabus
Technical product information
February 2012
DELTA isystem wall switch single
wall switch double
wall switch triple
Technical manual UP 22x/2, UP 22x/3 and UP 22x/5, 8 pages Siemens AG
Infrastructure & Cities Sector, Building Technologies
Update: http://www.siemens.com/gamma Siemens AG 2012 Control Products and Systems
Subject to change without further notice P.O. Box 10 09 53, D93009 Regensburg
2.16.1.11/2
connection between the wall switch and the bus cou
pling unit (BTM) is established via the Bus Transceiver In
terface (BTI).
Bus coupling unit (BTM) and the design frame “DELTA
line”, “DELTA vita”, or “DELTA miro” are not included and
therefore have to be ordered separately (see current
catalog).
Common functions
Switch buttons
Depending on the model a switch provides two to six
switch buttons (figure 1: A1, A2, B1, B2, C1, C2), which
horizontally function as a switch pair (A to C).
A2
A1
A1
B1
A1
B1
A2
B2
A1
B1
C1
A2
B2
C2
Horizontally aligned buttons may be used as a pair of
buttons (e.g. for defined switching/dimming, or control
of shutters and blinds, i.e. with the left button light is
turned on and with the right button light is turned off),
or as single buttons for sending values, singlebutton
switching/dimming or single button control of blinds.
Each individual switch button (A1, A2, B1, B2, C1, C2)
may be assigned one of the following functions:
• Switching (on, off, toggle)
• door bell function
• single button dimming
• single button control of solar protection (blinds, roller
shades)
• 1bit scene control (scene 1 or 2: recall / save)
• 8bit scene / effect control (recall, recall / save)
• Send value (8bit value, percent)
• Send value (16bit value, temperature value, brightness
value)
• Forced control
Depending on the selected main function another func
tion may be executed either additionally after a time de
lay (time delay configurable from 100ms to 655s) or al
ternatively when the button is pressed for a longer pe
riod.
When switch buttons are configured as a pair then this
button pair may be assigned one of the following func
tions:
• Dualbutton dimming with stop telegram
• Dualbutton control of solar protection (blinds, roller
shades)
• Send variable percent value
• Send variable 8bit value
• 1bit scene control (scene 1 and 2: recall / save)
• 8bit scene / effect control (recall / save)
• Forced control
Depending on the selected main function another func
tion may be executed additionally after a time delay
(time delay configurable from 100ms to 655s).
These options are available as additional or alternative
functions for single buttons or button pairs:
• Switching (on)
• Switching (off)
• Send percent value
• Send 8bit value (0…255)
• Send temperature value
• Send brightness value
• Send 16bit value (0…65535)
• 1bit scene control (scene 1: recall / save)
• 1bit scene control (scene 2: recall / save)
• 8bit scene / effect control: recall
• Forced on
• Forced off
• Deactivate forced control
Orientation lighting
The orientation light (LED) of the device may be turned
on or off continuously or depending on a status object.
These configuration options are available for the orienta
tion light (LED):
• LED permanently off
• LED permanently on
• LED indicates IR activity (only for switch with IR re
ceiver)
• LED indicates user operation
• LED indicates long button press
• A binary status object controls the LED for each status
value on (=1) or off (=0) respectively to either
o on
o off
o flash, slowly (0,3 Hz)
o flash, moderately (1 Hz)
o flash, fast (5 Hz)
• An analog status object (8bit value [0...255], percent
value, 16bit value [0...65535], temperature value