Function data
Rated pressure
1.6 MPa (PN 16; PS 16)/2.5 MPa (PN 25;
PS 25)
Mounting position Any
Mounting location Return
Nominal
flow q
p
Installa-
tion
length
Connec-
tion
Maximum
flow q
s
Minimum
flow q
i
Response
threshold
(variable)
Pres-
sure
loss at
q
p
Kv flow
rate at
Δp 1 bar
Kv flow
rate at
Δp 100
mbar
Weight
m
3
/h mm G/DN m
3
/h l/h l/h mbar m
3
/h m
3
/h kg
0.6 110 G ¾ 1.2 6 2.4 150 1.5 0.5 1
0.6 190 G 1 1.2 6 2.4 150 1.5 0.5 1.5
0.6 190 DN20 1.2 6 2.4 150 1.5 0.5 3
1.5 110 G ¾ 3 15 6 150 3.9 1.2 1
1.5 130 G 1 3 15 6 160 3.8 1.2 1.5
1.5 190 G 1 3 15 6 160 3.8 1.2 1.5
1.5 190 DN20 3 15 6 160 3.8 1.2 3
2.5 130 G 1 5 25 10 200 5.6 1.8 1.5
2.5 190 G 1 5 25 10 210 5.3 1.7 1.5
2.5 190 DN20 5 25 10 210 5.3 1.7 3
3.5 260 G 1¼ 7 35 14 55 15 4.7 3
3.5 260 DN25 7 35 14 55 15 4.7 5
6 150 G 1¼ 12 60 24 190 14 4.4 3
6 260 G 1¼ 12 60 24 140 16 5.1 3
6 260 DN25 12 60 24 140 16 5.1 5
10 200 G 2 20 100 40 130 28 8.8 2.6
10 300 G 2 20 100 40 110 30 9.5 4
10 300 DN40 20 100 40 130 28 8.8 7
15 200 DN50 30 150 60 95 49 15.4 5
15 270 DN50 30 150 60 110 45 14.3 8
25 300 DN65 50 250 100 105 77 24.4 11
40 300 DN80 80 400 160 160 100 31.6 13
60 360 DN100 120 600 240 115 177 56.0 22
150 500 DN150 300 1500 600 120 433 136.9 50 *)
*) Measuring insert 4 kg
Tolerance in the event of pressure drop: +/- 5%