Module WZU-MB G4 can be used in both slots. Always plug module WZU-MI into slot 1.
M-bus module with 2 pulse inputs
WZU-MI
Function description
In addition to the M-bus connection facility, the WZU-MI module has 2 pulse inputs to con-
nect metering pulses from hot and cold water meters with Reed contact, relay or open collec-
tor. The cumulated volume is calculated based on the pulses and the set pulse valency,
stored in the processor unit at 5-minute intervals and passed on via M-bus.
NOTICE
The volume values calculated by the meter from the pulse inputs cannot be officially cali-
brated.
In addition to possible power supply from the M-bus connection, the WZU-MI module is
equipped with a battery. It powers the module processor and the pulse input, if no M-bus
voltage is applied. Either isolated contacts (e.g. relay or Reed contacts) or electronic trans-
mitters (open collectors) can be used as pulse transmitters for the pulse inputs. If an open
collector circuit is used as the transmitter of the pulse inputs, the cable must always be elec-
trically isolated from the M-bus inputs of the WZU-MI module.
BACnet/Modbus module
WZU-485E-BAC
WZU-485E-MOD
The processor unit uses both modules to communicate over ModBus® or BACnet
TM
.
The ModBus® module is suitable (and preconfigured) for data transmission per the Mod-
Bus®-RTU protocol over RS485.
The BACnet
TM
module is suitable (and preconfigured) for data transmission per the BAC-
net
TM
protocol over RS485 and BACnet
TM
MS/TP.