Scope of delivery
Operating and installation instructions in multiple languages are included with the ultrasonic
heat and heat/cooling meters.
Languages
The instructions are supplied in 18 languages:
Bulgarian, Chinese, Croatian, Czech, Dutch, English, French, German, Greek, Hungarian,
Italian, Norwegian, Polish, Russian, Slovakian, Slovenian, Spanish, and Turkish.
Notes
Mounting
Flow measuring section
The mounting position is optional, the mounting location (return) must be in accordance with
the type of meter used.
NOTICE
The flow measuring section must be installed in the return on types UH50-A.., UH50-C..,
and UH50-G...
Settling paths are not required, neither upstream of nor downstream from the meter.
Thoroughly flush the plant prior to installing the meter.
Install the flow measuring section between 2 shutoff valves with the arrow pointing in the di-
rection of flow. The sensors must be mounted in the same water circuit as the flow measur-
ing section (observe mixing). Do not separate, shorten, or extend the lines.
Connect the individual wires according to the wiring diagram printed on the meter.
The sensors can be fitted in T-pieces or ball valves, or can be immersed, either directly or in
pockets (observe all national regulations).
NOTICE
In Germany, the temperature sensors must be installed submerged for meters to q
p
6 and
to PN16. Immersion sleeves only have to be used in case of higher stress levels.
In any case, the end of the sensors’ probe must extend to at least the pipe center. Tempera-
ture sensors and fittings must be sealed to prevent tampering. Overpressure must prevent
cavitation across the entire measuring range, that is, at least 1 bar with q
p
and approximately
3 bar with q
s
(at 80 °C).
Only authorized personnel are allowed to remove and replace calibration seals when carry-
ing out service work.