Data Sheet for Product

44
Smart Infrastructure
CE2N5324en
2021-03-
19
Communication
Pulse module
WZU-P2
Pulse outputs
Number of outputs per module
Standard pulses
Pulse value
Pulse length
Period duration
Pulse for operating states
Pulse duration for "Ready"
Pulse duration for "Fault"
Period duration
Fast pulses
Pulse length
Max. pulse frequency
Fast pulses
Pulse length
Max. pulse frequency
Type
Voltage
Current
Classification per EN 1434-2
Voltage drop
Classification per EN 1434-2
Voltage drop
Dielectric strength
2
For energy, volume and tariff register
1 kWh, 10 kWh, 1 MJ, 10 MJ, 100 MJ,
0.1 m
3
, 1 m
3
per pulse
100 ms conducting
>200 ms
0.1…0.25 ms conducting
Constantly non-conducting
500 ms
If 1 pulse module is fitted
2…100 ms in increments of 1 ms
33 Hz
If 2 pulse modules are fitted
5…100 ms in increments of 5 ms
33 Hz
Open collector
Max. DC 30 V
Max. 30 mA
OB
Approx. 1.3 V at 20 mA
OC
Approx. 0.3 V at 0.1 mA
500 V
eff
against ground
M-bus module
WZU-MB G4
WZU-MI
M-bus slave interface
Voltage
Power consumption
Address
Baud rate
Polarity
Galvanic isolation
From meter
From pulse inputs
As per EN 1434-3 and EN 13757-2 /-3
Max. DC 50 V
1 M-bus load (1.5 mA)
Primary or secondary
300, 1200, 2400, 4800, 9600 baud
Any
Yes
No