Data Sheet for Product
24
Smart Infrastructure
CE2N5324en
2021-03-
19
For tariff T9 (cooling energy/heat meter)
No tariff register active
Tariff register 1 active
Tariff register 2 active
The type of tariff and the associated parameters are displayed in service loop 4.
For T2, T3, T4, T5, and T6
At 2-second intervals with threshold value 1/2/3
For T7
For T8
For T9
At 2-second intervals
For T10
Switching times at 2-second intervals
For T11
For T12
The contents of the tariff registers is displayed in the user loop after the energy.
For tariffs T2, T3, T4, T5, T6, T10, T11, and T12
Tariff register 1
Tariff register 2
Tariff register 3 (not for T12)
For tariff T7
For tariff T8
For tariff T9
Log functions
In the internal logbook, meteorologically relevant events (errors, states, actions) are stored in
chronological order with the time of occurrence. The acquired events are predefined. Log-
book data cannot be deleted.
Each event is stored in a separate 4-level shift register; the overflows are transferred to a 25-
level circulating buffer. So that at least the last 4 times can be traced for each event.
In a monthly register, the error states are stored for the current month and the past 18
months (without time stamp).