Data Sheet for Product
13
Smart Infrastructure
CE2N5324en
2021-03-
19
Permissible module combinations
AM Analog module Step 1:
Slot for module 2 is equipped with...
MB G4 M-bus module
MB MI M-bus module
RF RF module
LoRa LoRaWAN
module
BACnet BACnet module
Modbus Modbus module
NB-IoT NB-IoT module
GPRS GPRS module
AM (3) Pulse module MB G4 GPRS RF LoRa
"Standard" "Fast" (1)
Step 2:
Slot for
module #1
can be
equipped
with...
AM Yes Yes Yes Yes No Yes Yes
Pulse module (2)
"Standard"
Yes Yes Yes Yes Yes Yes Yes
MB G4 Yes Yes Yes Yes Yes Yes Yes
MB MI Yes Yes Yes Yes No Yes Yes
BACnet No No No Yes (4) No No No
Modbus No No No Yes (4) No No No
Restrictions:
* Only 1 module with fast pulses is possible; and only permissible in slot 2;
min. pulse duration:
● 2 ms, if pulse module 1 is not fitted
● 5 ms, if pulse module 1 is fitted
**) Subsequent mounting of a further pulse module in module slot 1 can result in changed
output values for module 2!
(1) Pulse length of the fast pulses min. 5 ms
(2) The first and second channel can be configured individually!
(3) Do not insert the analog module in slot 2 on meters powered by AC 110/230 V
(4) Polling interval < 10 minutes required D cell (6 years) or power supply.