Bedienungsanleitung

Note: The cables used should be as short as possible
and their length must not exceed 10 m.
Note: Both display range and data displayed can differ
from this description depending on the meter parame-
terization. Certain button functions can also be blocked.
Head of the loop
Type “MI / G4” in slot “module 1”
M-Bus Primary address for slot “module 1”
Note: For modules with firmware version v5 and
higher, setting the Modbus address must be done
using the WZU-485ConfigurationTool (see chapter
6.2).
Requirements:
Micro-USB (type B) to USB cable
Computer with Windows OS
Software “WZU-485 Configuration Tool”; can be down-
loaded from www.landisgyr.eu
Attention: The module’s power supply must be
switched off before the module is connected to a PC
via USB cable.
Note: The micro-USB interface is used for setting the
communication protocol, communication speed, parity
and Modbus address.
Note: For battery-powered meters: Operating the
communication module with a read-out interval of less
than 10 minutes requires a D-cell battery for 6 years.
General information
Communication protocol
Modbus RTU on RS485
Modbus address range
1 247
Transmission rate
2400 / 4800 / 9600 / 19200 bps
Communication address
M-Bus primary address of T550
(Loop 4: )
Data refreshing
Parity
Number of stop-bits
Stand-by mode: 60 min
In operation: After every data request, up to 10s
Even / odd / none
1
Default settings
Transmission rate
9600 bps
Modbus Parity
even
Communication address
0 (meter default; must be changed)
RS485 information
HW network connection
RS485: A+, B-, GND
communication signal inputs (A, B) are protected
against short-term (pulse) overload
Bus termination
use external resistor (120 Ohm)
Power supply
Alternating current
permissible range AC 16...28 V
Direct current
permissible range DC 10...32 V
Consumption
<50mA (typically <20 mA / 24 V)
Recommended fuse
fuse T 100 mA
Galvanic Isolation
From the meter
yes
From the RS485 network
no
[1]
[2]
[3]