Hardware functions
3.6.3 Software parameterization
“External PT100” should be selected in the parameterization software (HART-Com-
municator or SIMATIC PDM) as the type of reference point compensation.
3.6.4 Order
• Add code S02 or 23 to the order number of the SITRANS TW
• Order as accessory under order number 7NG3092-8AV
3.7 Current/voltage measurement by U/I input plug
7NG3092-8AW
3.7.1 Application and use
It serves in devices with the ordering designation 7NG3242-0***0 as a measuring
set for:
• voltage measurement in the measuring range: -1.2 to 10 V DC or
• current measurement in the measuring range: -12 to 100 mA DC
The basic accuracy of the U/I input plug is: 0,1 %.
The minimum span is for:
• voltage measurement (measuring range -1.2 to 10 V): 0.05 V
• current measurement (measuring range -12 to 100 mA): 0.41 mA
WARNING
The U/I input plug may not be used in hazardous (explosive) areas.