User Manual

CA1N1328E / 11.1998 Siemens Building Technologies
2/2 Landis & Staefa Division
The housing of the TRM2... room thermostats is made of plastic. A captive screw,
invisible from the front, allows easy fitting of the cover.
Cable is introduced through an opening in the rear plate, or through the top.
Mounting instructions are enclosed with the room thermostat (Ref. 35200).
The sensor should be mounted at a height of approximately 1.5 m above floor level and
at least 0.5 m from the corner of the room. Do not install the sensor in a position where it
will be exposed to direct sunlight. Avoid locations where there may be undue influence
from heat or moisture, such as near doors, windows, chimneys etc., and locations with
inadequate air circulation (in recesses, behind furniture or curtains etc.).
Setpoint 5 ... 30 °C
Switching differential
t ± 5 K
with thermal feedback ± 1 K
Output SPDT
Contact rating Max. AC 250 V
– Heating (Terminal 1) Max. 10 A resistive, max. 3 A inductive
– Cooling (Terminal 5) Max. 3 A resistive, max. 1 A inductive
Protection class II (VDE*)
Protection standard IP30 to IEC529
Radio interference suppresion in accordance with VDE 0875
Ambient temperature:
– Operation 0 ... 50 °C
– Storage / transport – 20 ... 50 °C
Weight (incl. packaging) 0.1 kg
Conformity CE requirements
* German Association of Electrical Engineers
The thermostat can be operated with thermal feedback (neutral wire on Terminal 4).
TRM2 TRM2S
50315
1
2
3
4
5
L
N
t
50314
1
2
3
4
5
L
N
t
= Heating
= Cooling
All dimensions in mm
60
4
12
24
70
70168
15
10
5
20
25
30
°C
74
Mechanical design
Mounting notes
Technical data
Connection
terminals
Dimensions
1998 Siemens Building Technologies Ltd.
Caution :
Observe the technical data for
the switching contacts :
AC 250 V / 10(2) A