User's Manual

TC12 Installation, Commissioning & Maintenance Handbook
2 TC12 INST
2.1 SPECIFICATION
2.1.1 Mains voltage ranges
The Instation will work over: 98 – 132 V RMS
198 – 264 V RMS
Note. The voltage range of the PC used in the Instation should be checked in the
manufacturer's literature and note should be taken of any links/switches
that need setting for different voltage ranges.
2.1.2 Mains frequency range
All TC12 equipment will work from 47 Hz to 63 Hz
2.1.3 Mains current
Instation Cabinet and PC without racks 1.0 A @ 240 V
ITU Rack (Fully equipped) 200 mA @ 240 V
igital Output Rack (Fully equipped) 4.5 A @ 240 V
s at 24 V 25 mA per LED
put lly equipped) 2.75 A @ 240 V
r LED
he figures above are added together for the system used:
A
.0 + 0
An ITU cabinet with two 15mA Digital output racks will take:
+ 2.75 + 2.75 = 6.5 A
2.1.4 Temperature and humidity requirements
The ITU will work over: 0 °C to 40 °C
Humidity: 20%-80% non-condensing
ATION
D
1024 LED
Digital Out Rack (Fu
51024 LEDs at 24 V 1 mA pe
T
n ITU cabinet with two ITU racks will use:
.2 + 0.2 = 1.4 A 1
666/HE/43100/000 Page 10 Issue 9