Allocate aspect drive identity to each current sensor:
NOTE: No aspect drive required for regulatory sign.
KAD 1 = 0 :sensor 1 is phase A
KAD 2 = 1 :sensor 2 is phase B
KAD 3 = 2 :sensor 3 is phase C
KAD 4 = 3 :sensor 4 is phase D
KAD 5 = 4 :sensor 5 is phase E
KAD 6 = 5 :sensor 6 is phase F
KAD 7 = 6 :sensor 7 is phase G
KAD 8 = 7 :sensor 8 is phase H
KAD 9 = 7 :sensor 9 is phase H, Wait drive
Select normal lamp monitoring (not RLM) on vehicle phases:
Note: Sensors 8 and 9 do not monitor vehicle phases and so they are configured
for normal lamp monitoring by default - their configuration does not need
to be changed.
KRE 1 = 0 :sensor 1
KRE 2 = 0 :sensor 2
KRE 3 = 0 :sensor 3
KRE 4 = 0 :sensor 4
KRE 5 = 0 :sensor 5
KRE 6 = 0 :sensor 6
KRE 7 = 0 :sensor 7
Turn off dim/bright checks:
KDP = 0
Reset lamp monitor
KLR = 1 :Resets LMU, and LMU relearns the lamp
characteristics.
Enable lamp monitor facility
KLE = 1