User's Manual

TC12 Installation, Commissioning & Maintenance Handbook
Allocate function of each current sensor:
KPT 1 = 1 :current sensor 1 monitors a vehicle phase
KPT 2 = 1 :current sensor 2 monitors a vehicle phase
Allocate mains state inputs for each current sensor:
Note: Input numbers 1 to 32 on the buffered input connector are referenced as 0
to 31 on the handset commands.
KMS 0 1 = 31 :mains state for sensor 1 is on
:digital input 32
KMS 0 2 = 30 :mains state for sensor 2 is on
:digital input 31
Allocate phase identity to each current sensor:
KAD 1 = 0 :sensor 1 is phase A
KAD 2 = 1 :sensor 2 is phase B
Select normal lamp monitoring (not RLM) on vehicle phases:
KRE 1 = 0 :sensor 1
KRE 2 = 0 :sensor 2
Reset the lamp monitor and enable lamp monitoring:
KLR = 1 :reset lamp characteristics
KLE = 1 :enable lamp monitoring
Example 2 - 4 phase controller with signs
Description: Four phase intersection controller with no lamp dimming. Two of
the phases are vehicle and two are pedestrian. The controller also
drives regulatory signs and two switched signs.
The wait indicators in this example are monitored using their own
current sensors, separately from those used to monitor the
pedestrian red and green (see example 3 for combined wait and
pedestrian monitoring on one current sensor).
The configuration commands are detailed below.
Enable LMU write access:
AMB = 35
NEC = 249
Allocate function of current sensor 1 to 9:
666/HE/43100/000 Page 118 Issue 9