Technical data
Configure the unit
16
Siemens Building Technologies
Fire Safety & Security Products 12.2007
6.4.1 TCP/IP
Prerequisites:
z APN (see section 4.3: TCP / IP) of your service provider.
z Domain name or an IP address.
1. Click the
button.
Î The window Internet configuration will open:
Fig. 4 Internet Configuration
Button or Field Description
Access point name Displays the internet service provider (APN address)
Event’s table Displays the available events to trigger the IGS6-10 modem.
Add Add a new entry to the list.
Remove Removes an unwanted number.
Properties Edit the existing account and IP Address (or phone number)
Up
Down
The top number is dialed first and if unavailable continues to the next in
sequence. Use these buttons to move the numbers up and down the list
so that you can place them in the required sequence.
There are 2 ways to operate the IGS6-10 modem:
– As backup
– Independently
Backup
The backup will operate at the following cases:
z Physical loss of phone line.
z Dialer: Unanswered.
z Dialer: No Kiss-off.
If you want the IGS6-10 modem to operate only as backup to PSTN and the inte-
grated dialer of the IC60:
2. Disable the setting “Enable Dialer: P175E 1E in the IC60.
3. Select the checkbox Only while PSTN Fail/Dialer Failure! (this option can be
checked separately for every protocol).