Installation Instructions
Installation Instructions
Document No. 553-680
October 9, 2019
TC Compact 36
Siemens Industry Inc. Page 1 of 4
Item Number: 553-680(CA)
Danger/Warning/Caution Notations
DANGER
Electric shock, death, or severe
property d
amage may occur if you
do not perform a procedu
re as
specified.
WARNING:
Personal injury or property damage
may occur if you do not foll
ow a
procedure as specified.
CAUTION:
Equipment damage or loss of data
may occur if you do not follow a
procedure as specified.
Product Numbers
TC36-E.T
TC Compact, 36 point, BACnet/IP or
MS/TP ALN
TC36-EF.T
TC Compact, 36 point, BACnet/IP or
MS/TP ALN includes TX-I/O and FLN
support licenses
For more information, see the TX-I/O Module Installation
Instructions (553-141) and TX-I/O Power Supply and
Bus Modules Installation Instructions (553-142).
Product Description
The TC Compact Series communicates with other field
panels or workstations on a peer-to-peer Automation
Level Network (ALN), or on the Field Level Network
(FLN) and supports the following communication
options:
• BACnet/IP over 10/100 MB Ethernet networks
• BACnet MS/TP on RS-485 networks
Required Tools and Materials
• Wire stripper/side cutter
• Small flat-blade screwdriver
• Phillips screwdriver
• Electric drill and Phillips driver bit
• Level
• Tape measure
• Digital multimeter (DMM)
• Black marker
• Masonry drill bit (to mount on concrete or
masonry)
• Four wall anchors (to mount on concrete or
masonry)
• Optional DIN rail (1.38" × 0.3" × 0.04" (35 mm ×
7.5 mm × 1 mm))
Included Materials
The following screws are included for mounting the TC
Compact without a DIN rail:
• Four No. 8-18 × 3/8” self-tapping Phillips screws
• Four No. 8-18 × 3/4” self-drilling Phillips screws
• Two No. 8-18 × 1-3/4” self-drilling Phillips screws
Expected Installation Time
20 minutes
Prerequisites
CAUTION:
No power wiring is connected to the field
panel controller or other TX-I/O components
at this time.
The TX-I/O island bus must be mounted on a
DIN rail (1.38" × 0.3" × 0.04" (35 mm × 7.5
mm × 1 mm)).
• If mounting in an enclosure:
− Enclosure is installed, DIN rail included.
− The power source is installed, as applicable.
− The power is OFF.
• All necessary wiring is pulled and terminated per
the layout drawing.
• Power and communication wiring is terminated to
the removable plugs supplied with the devices.
CE Compliance Requirements
Must be installed inside a metal enclosure rated at IP20
minimum.
Energy Management Applications
For energy management only (low voltage Class 2), the
TC Compact may be mounted on a flat surface.