Installation Instructions

Installation Instructions
Document No. 553-652
October 1, 2016
TC Compact Series
Item Number 553-652(EA) Page 1 of 4
Product Description
The TC Compact Series communicates with other field
panels or workstations on a peer-to-peer Automation
Level Network (ALN). The following communication
options are supported:
Native BACnet/IP communications over 10/100
MB Ethernet networks
Native BACnet MS/TP on RS-485
The TC Compact is available in 16- or 24-point versions
with optional support for FLN devices (requires
additional license and TC Compact model with both an
Ethernet and an RS-485 port). Selected models also
include an extended temperature range for the control of
rooftop devices.
For information on the TC Compact Series
with an extended temperature range, see the
TC Compact Series Extended Temperature
Range Option Installation Instructions (553-
653).
Product Numbers
TC16.2-EF.T TC Compact, 16 point, BACnet/IP ALN,
MS/TP FLN
TC16.2-EF32.T TC Compact, 16 point, BACnet/IP ALN,
RS-485 Enabled
TC24.2-EF.T TC Compact, 24 point, BACnet/IP ALN,
MS/TP FLN
TC24.2-EF32.T TC Compact, 24 point, BACnet/IP ALN,
RS-485 Enabled
PXA-DIN16KIT Accessory kit with four 16" (406 mm)
DIN rails
Warning/Caution Notations
WARNING:
Personal injury or property damage
may occur if you do not follow a
procedure as specified.
CAUTION:
Equipment damage or loss of data
may occur if you do not follow a
procedure as specified.
Required Tools and Materials
Wire stripper/side cutter
Small flat-blade screwdriver
Phillips screwdriver
Electric drill and Phillips driver bit
Level
Tape measure
Digital multimeter (DMM)
Black marker
Masonry drill bit (to mount on concrete or
masonry)
Four wall anchors (to mount on concrete or
masonry)
Optional DIN rail (1.38" W × 0.276" H × 0.04" D
(35 mm W × 7 mm H × 1 mm D))
Included Materials
The following screws are included for mounting the TC
Compact without a DIN rail:
Four No. 8-18 × 3/8” self-tapping Phillips screws
Four No. 8-18 × 3/4” self-drilling Phillips screws
Two No. 8-18 × 1-3/4” self-drilling Phillips screws
Expected Installation Time
20 minutes
Prerequisites
CAUTION:
No power wiring is connected to the TC
Compact at this time.
If mounting in an enclosure:
Enclosure is installed.
The power source is installed, as applicable.
The power is OFF.
All necessary wiring is pulled and terminated per
the layout drawing.
Power and communication wiring is terminated to
the removable plugs supplied with the devices.