Compatibility with the TALON Automation System
14
| 93
Siemens Industry, Inc.
Owner's Manual
588-682
Building Technologies
2019-01-25
TX-I/O Power Supply and Bus Modules
Product Number
Description
TXS1.12F4 TX-I/O Power Supply, 1.2A, 4A Fuse
TXS1.EF4 TX-I/O Bus Connection Module, 4A Fuse
Accessories
Product Number
Description
TXA1.K12 One set of address keys, numbers 1-12.
TXA1.K24 One set of address keys, numbers 1-24.
TXA1.K-48 One set of address keys, numbers 25-48.
TXA1.K-72 One set of address keys, numbers 49-72.
TXA1.LLT-P100 Labels for TX-I/O, 100 sheets/pack, letter format.
TXA1.LH Replacement label holders.
Compatibility with the TALON Automation System
TALON BACnet is compatible with the BACnet/IP protocol.
CAUTION
When working on a network with multiple firmware revisions, always connect to the
operator interface at the field panel with the newest firmware revision. Otherwise, you
cannot view features in newer firmware revisions, or the field panel may coldstart.
TCP/IP Protocol Compatibility
TC Compact Series controllers with BACnet/IP ALN provide the following:
100% compatibility with the TCP/IP protocol suite.
Support of Dynamic Host Configuration Protocol (DHCP) and Domain Name
Servers (DNS).
Support and auto detection of 10Base-T and 100Base-TX Ethernet.
Required IP Addresses
TALON BACnet/IP ALN uses:
One IP address per device (field panel or workstation).
One additional shared IP address per ALN for the multicast group (when using
multicast optimization).
Device Registration
Devices register with the DHCP server and Domain Name Server, if either is present.