Operating Instructions

Table Of Contents
Chapter 2Hardware Features
PX Series Enclosures and Service Boxes
72
| 93
Siemens Industry, Inc.
Owner's Manual
588-682
Building Technologies
2019-01-25
Figure 35: PX Series Service Box Connectors.
Each Service Box distributes the total 24 Vac power provided to the plug-in
terminations on the left side.
Two Class 1 power-limited terminations distribute up to the total power to
controllers and power supplies inside the same enclosure.
Earth ground is provided on the CTLR termination.
One Class 2 termination distributes up to 96 VA to auxiliary devices outside of
the enclosure.
Each 115VAC Service Box has a duplex outlet on the front to power accessory
devices such as modems and Portable Operator’s Terminals.
Product Numbers
Product Number
Description
PXA-SB115V192VA PX Series Service Box115V, 24 Vac, 50/60 Hz, 192 VA
PXA-SB115V384VA PX Series Service Box115V, 24 Vac, 50/60 Hz, 384 VA
PXA-SB230V192VA PX Series Service Box230V, 24 Vac, 50/60 Hz, 192 VA
PXA-SB230V384VA PX Series Service Box230V, 24 Vac, 50/60 Hz, 384 VA
PXA-ENC18 18" Enclosure (Utility Cabinet) (UL Listed NEMA Type 1 Enclosure)
PXA-ENC19 19” Enclosure (UL Listed NEMA Type 1 Enclosure)
PXA-ENC34 34” Enclosure (UL Listed NEMA Type 1 Enclosure)