Operating Instructions
Table Of Contents
- How to Use This Manual
- Chapter 1—Introduction
- Chapter 2—Hardware Features
- 16- and 24-Point Compact Series Diagram
- 36-Point Compact Series Product Diagram
- Supported Point Types
- Compact Series Backup Batteries
- Using Auto Restore and Database Backup to Flash
- Memory
- Communication Connections
- Compact Series Smoke Control Application Requirements
- HOA (Hand-Off-Auto) Upgrade Kits
- PXM10S/T Product Overview and Description
- Unitary Equipment Controller
- TX-I/O Product Range Overview
- PX Series Enclosures and Service Boxes
- Chapter 3—Applications
- Chapter 4—Troubleshooting
- Glossary
- Index
Chapter 2—Hardware Features
HOA (Hand-Off-Auto) Upgrade Kits
0
45 |
93
Siemens Industry, Inc.
Owner's Manual
588-682
Building Technologies
2019-01-25
NOTE:
Default user account login information for PXM10S or PXM10T is on a per ALN
account basis.
If your network contains an assortment of field panels with Firmware Revisions earlier
than 3.2.2, the AutoLogin account is not replicated or passed onto other field panels.
For more information about workstation user accounts, see the TALON View
Online
Help
system.
Configuring AutoLogin at the HMI with HyperTerminal
Complete the following steps to configure an automatic login using HyperTerminal at
the host field panel’s HMI.
You must be logged into the field panel with an account that has Edit level access
permission to the user's access group.
HMI
S, U, A, E, A
(System, Users, Accounts, Edit, Add)
Prompt/Field
Option/Entry
Description
User initials Type the new user’s initials.
Account name Type the account name.
Password Type a password for the user.
Verify password Retype the password.
System, User namespace S View System point names.
U View User point names. (default setting)
Access group(s) All groups. (default setting).
A single access group. Valid value 1 through 30.
Multiple access groups.
Valid values 1 through 30 separated by commas, or use
two periods to indicate a range (for example,
1..4,7,9,12..20).
Privilege
NOTE:
Auto User accounts need access to
Point and Alarm ONLY.
Point
N
(No_access)
R
(Read_only)
C
(Command)
E
(Edit) (default setting)
Alarm
N
(No_access)
R
(Read_only)
C
(Command)
E
(Edit) (default setting)
Trend
N
(No_access)
R
(Read_only)
C
(Command)
E
(Edit) (default setting)
Application
N
(No_access)
R
(Read_only)
C
(Command)
E
(Edit) (default setting)