Operating Instructions

Table Of Contents
Chapter 2Hardware Features
HOA (Hand-Off-Auto) Upgrade Kits
40
| 93
Siemens Industry, Inc.
Owner's Manual
588-682
Building Technologies
2019-01-25
INFO button provides one touch access to detailed system information for points.
Manual and automatic login option for enhanced security or easy access.
View point information and status, view and acknowledge alarms, and
command/release local field panel points.
Point Monitor Can customize a group of points to continuously display and
refresh with updated values (PXM10S only).
Multi-language (English, Simplified Chinese, French, and Korean) support.
The PXM10S and PXM10T modules can also be mounted on the inside or outside
of an enclosure door, using an optional accessory sold separately.
Communication Connections
A field panel fully powered and running Firmware Revision 3.2.2 or later, recognizes
the PXM10S and PXM10T modules within approximately 5 seconds of connection.
Prior to that, the Operator Display is not operational.
If a field panel is coldstarted or it’s the first time the panel is powered up, it takes
approximately 15 to 30 seconds after connection before the PXM10S and PXM10T
module is operational.
Requirements
System Requirements
The PXM10S and PXM10T modules can be used with Compact platforms (TC-36, TC-
24, and TC-16), as well as with the TC Modular field panels.
All hardware must be installed.
Power must be available to all devices.
System components must be installed, running, and checked out by an appropriate
system representative.
Hardware Platform
The PXM10T and PXM10S modules can be used on all Siemens Compact and
Modular series controllers. An additional connecting ribbon cable (part number PXA-
HMI.CABLEP5) is required when mounting to a PXC16 or PXC24.
Firmware Platform
The PXM10T and PXM10S modules are compatible with all Siemens Compact and
Modular series controllers using Firmware Revision 3.2.2 or later (proprietary
protocol/BACnet).
Application Menus
The following application menus are provided with the PXM10S and PXM10T modules.
Login
Alarms
Points (Command and Release)
Point Monitor
Logoff
Settings