Installation Instructions
Document No. 553-169T
Installation Instructions
July 22, 2015
Page 2 of 5 Siemens Industry, Inc.
Prerequisites
CAUTION
No power wiring is connected to the
field panel controller at this time.
⚫ If mounting in an enclosure:
– Enclosure is installed.
– The power source is installed, as applicable.
– The power is OFF.
⚫ All necessary wiring is pulled and terminated per
the layout drawing.
⚫ Power and communication wiring is terminated
to the removable plugs supplied with the
devices.
Power Requirements
One of the following power sources is pulled to the
enclosure:
⚫ 120 Vac, 60 Hz and terminated at the 115V PX
Series Service Box.
⚫ 230 Vac, 50/60 Hz and terminated at the 230V
PX Series Service Box.
⚫ 24 Vac, 50/60 Hz Class 1 power limited from a
third-party transformer and connected to a
terminal block.
CE Compliance Requirements
Must be installed inside a metal enclosure rated at
IP20 minimum.
Energy Management Applications
For energy management only (low voltage Class 2),
the TC Compact may be mounted on a flat surface.
Outdoor Applications
For outdoor applications, mount the rooftop TC
Compact UEC Models inside a NEMA-4 rated
enclosure or a similarly protected environment.
Applications Requiring a Secure
Enclosure
For any application requiring a secure enclosure,
mount the TC Compact inside a listed enclosure
along with a Service Box and Sidewall Kit, if needed.
Installation
WARNING
Turn OFF AC power at the circuit
breaker panel.
CAUTION
UL Listings require that NEC Class I
and Class II wiring be kept separate
from each other. Use separate
conduit and cable tie bars to
separate Class I Digital Output (DO)
wires from all other Class II wiring.
NOTE:
Securely fasten the TC Compact so that
it does not come loose when point
connectors are removed.
NOTE:
If you need to reinsert one of the
mounting tabs, see the TC Compact
Series Owner's Manual (588-682) for
instructions.
The TC Compact may be mounted either vertically
(with 24 Vac and DOs on the right) or horizontally
(with 24 Vac and DOs at the top).
Options for Mounting the Compact
Series
⚫ Select one of the following options for
installation:
Mount the controller on a DIN rail by using
the four slide-out mounting tabs.
Fasten the controller to a surface or
enclosure backplane with screws