Data Sheet for Product

Page 5 of 6
Siemens Industry, Inc.
D/A Resolution (analog out) 10 bits
AC Power and Digital Outputs NEC Class 1 Power Limited
Communication and all other I/O
NEC Class 2
Digital Output
Class 1 Relay, Form C (NO and NC
contacts)
Analog Outputs
Voltage (0-10 Vdc)
Universal Inputs (UI) and
Universal Inputs/Outputs (U)
Analog Inputs
Voltage (0-10 Vdc)
Current (4-20 mA)
1K Ni RTD @ 32°F (Siemens, JCI, DIN
Ni 1K)
1K Pt RTD (375 or 385 alpha) @ 32°F
10K NTC Type 2 or Type 3 Thermistor
100K NTC Type 2 Thermistor
Analog Outputs
0 to 10 Vdc @ 1 mA max
Digital Inputs
Pulse Accumulator
Contact Closure Sensing
Dry Contact/Potential Free inputs only
Digital Input (10 ms settling time)
Supports counter inputs up to 20 Hz,
minimum pulse duration 20 ms (open or
closed)
Super Universal (X)
Analog Inputs
Voltage (0-10 Vdc)
Current (4-20 mA)
1K Ni RTD @ 32°F (Siemens, JCI, DIN
Ni 1K)
1K Pt RTD (375 or 385 alpha) @ 32°F
10K NTC Type 2 or Type 3 Thermistor
100K NTC Type 2 Thermistor
Analog Outputs
0 to 10 Vdc @ 1 mA max
0 to 20 mA @ 650 Ω max
Digital Inputs
Pulse Accumulator
Contact Closure Sensing
Dry Contact/Potential Free inputs only
Digital Input (10 ms settling time)
Supports counter inputs up to 20 Hz,
minimum pulse duration 20 ms (open or
closed)
Digital Output
0 to 24 Vdc, 22 mA max.
(using external relay)
Shipping & Storage -13°F to 158°F (-25°C to 70°C)
Operating Temperature 32°F to 122°F (0°C to 50°C)
Operate in a dry location, which is protected from exposure to salt spray or other
corrosive elements. Exposur
e to flammable or explosive vapors must be
prevented.
Operating temperature
with rooftop
(extended temperature) option
-40°F to 158°F (-40°C to 70°C)
Relative Humidity 5 to 95% rh non-condensing
Mounting Surface Direct equipment mount, building wall, or structural member
CE Compliance
Must be installed inside a metal enclosure rated at IP20 minimum
UL UL916 PAZX
UL916 PAZX7
Agency Compliance FCC Compliance CFR47 Part 15, Subpart B, Class B