Installation Instructions

Document No. 553-652
Installation Instructions
July 15, 2011
Information in this document is based on specifications believed correct at the time of publication. The right is reserved to make changes as design
improvements are introduced. TALON and TALON View are registered trademarks of Siemens Industry, Inc. Other product or company names
mentioned herein may be the trademarks of their respective owners. © 2016 Siemens Industry, Inc.
Siemens Industry, Inc.
Building Technologies Division
1000 Deerfield Parkway
Buffalo Grove, IL 60089-4513
USA
1-847-215-1000
Your feedback is important to us. If you have
comments about this document, please send them to
sbt_technical.editor.us.sbt@siemens.com.
Document No. 553-168
Printed in the USA
Page 4 of 4
3. Align the TC Compact on the mounting surface and
mark the position of the mounting holes.
4. For installation in an enclosure, align the mounting
holes of the TC Compact with holes in the perforated
backplane.
5. Using wall anchors if necessary secure the controller
using the provided screws.
6. Continue with Completing the Installation.
Completing the Installation
CAUTION:
Do not connect the shield wire to the
connector.
Terminate only one end of the shield wire on
the enclosure earth ground.
terminal is connected to reference wire.
Protective ground terminal may be connected
to earth ground.
Do not connect the power or network
communication cable until instructed to do so
during start-up.
1. Terminate power wiring to the 24 Vac removable
plug.
2. If required, remove the RS-485 plug and terminate
the communication wiring.
3. Terminate point wiring to the appropriate
connectors.
CAUTION:
Adjacent point connections on the TC
Compact share a Common termination.
For specific wiring diagrams, see the TALON Wiring
Guidelines for Field Panels and Equipment Controllers
(588-581).
The installation is now complete.
The combined total of the external sensor
power outputs cannot exceed 200 mA.